  4、大于'''40次到9 kHz谐波差分模式下的电压失真'''
  '''4、大于40次到9 kHz谐波差分模式下的电压失真'''


'''限值:'''
'''限值:'''
第67行: 第67行:




  5、差分模式下的电压失真从9 kHz到150 kHz
  '''5、差分模式下的电压失真从9 kHz到150 kHz'''


5.1 '''9 kHz到30 kHz差分模式下的电压失真'''


5.1 '''9 kHz到30 kHz差分模式下的电压失真'''
'''限值:'''


Table 3 – Compatibility levels for voltage distortion in differential mode from 9 kHz to 30 kHz(a)
Table 3 – Compatibility levels for voltage distortion in differential mode from 9 kHz to 30 kHz(a)
第86行: 第87行:


5.2 '''30kHz到150 kHz差分模式下的电压失真'''
5.2 '''30kHz到150 kHz差分模式下的电压失真'''
'''限值:'''
Table 4 – Compatibility levels for voltage distortion in differential mode from 30 kHz to 150 kHz a
Table 4 – Compatibility levels for voltage distortion in differential mode from 30 kHz to 150 kHz a


{| class="wikitable"
{| class="wikitable"
第101行: 第104行:
* '''b''' At the transition frequency, the lower level applies
* '''b''' At the transition frequency, the lower level applies
* '''c''' The level decreases linearly with the logarithm of the frequency in the ranges 30 kHz to 50 kHz and 50 kHz to 1 50 kHz.
* '''c''' The level decreases linearly with the logarithm of the frequency in the ranges 30 kHz to 50 kHz and 50 kHz to 1 50 kHz.





2020年3月20日 (五) 13:39的版本

简介

IEC 61000-2-2 Electromagnetic compatibility (EMC) – Part 2-2: Environment – Compatibility levels for lowfrequency conducted disturbances and signalling in public low-voltage power supply systems

IEC 61000的本标准部分涉及传导电磁现象(主电源通信系统的干扰和信号)的频率范围为0 kHz至150 kHz,扩展频率高达148.5 kHz,专门用于干线信号系统。它给出了公共低压交流电的兼容性等级。额定电压最高电压为单相420 V或三相690 V,额定频率为50 Hz或60 Hz的配电系统。

本标准文档中规定的兼容水平针对公共连接点。当设备的电源输入端口从上述系统吸收电能时, 大多数情况下所受的骚扰强度与公共连接点相等, 但有些情况下却例外, 例如长距离供电的特定装置, 或者骚扰在由设备集成的装置内部产生或放大,在设备内部构成设备的设备中产生或放大的电磁现象。

本部分考虑的电磁现象包括:

  • 电压波动和闪烁;
  • 40次谐波及 40 次以下的谐波;
  • 40次以下的间谐波;
  • 较高频率下差模的电压畸变(高于40次谐波至150 kHz);
  • 电压骤降和电源短路中断;
  • 电压不平衡;
  • 瞬态过电压;
  • 电源频率变化;
  • 直流分量;
  • 电网信号,来自电源通信系统(MCS)的信号。

测试项目

1、电压波动和闪烁 

限值:

兼容水平为: 短期: P st =1 ; 长期: P lt =0.8

2、谐波

本部分中, 谐波的兼容水平主要针对稳态和准稳态谐波, 并给出 其长期影响和短期影响的参考值。 长期影响主要指谐波在电缆、变压器、电动机、电容等设备上引起的热效应, 这主要由 持续时间10 min及以上的谐波水平引起。 短期影响, 主要指持续时间 3 s 及以 下的谐波水平对某些敏感设备的骚扰影响, 暂态不包括在内。

限值:

  • 对于长期影响, 对应的总谐波畸变的兼容水平为THD=8%
  • 对于短期影响, 单次电压谐波分量的兼容水平由 表 1 中的限值乘以系数 k , 此时, 对应的总谐波畸变的兼容水平为 THD =11%
3、间谐波

涉及间谐波电压的电磁骚扰认识仍然在发展中。 本部分兼容水平仅针对接近基波频率的间谐波电压( 50 Hz~60 Hz ), 这种间谐波电压会对供电电压调幅。在这些情况下,一些对电压平方值敏感的负载,特别是照明装置,会产生差频效应,导致闪烁。差频是指两个同时发生的电压在频率上的差值, 例如间谐波频率和基波频率。

限值:

单个间谐波电压的幅值和基波幅值的比值作为差频的函数,参考IEC61000-2-2:2002+AMD1:2017+AMD2:2018的Figure 2 Figure 2 – Compatibility level for interharmonic voltages relating to flicker (beat effect)


4、大于40次到9 kHz谐波差分模式下的电压失真

限值:

Frequency range(kHz) Compatibility levels(%)
2 (2,4) a to 3 1 ,4
3 to 9 1 ,4 to 0,65 b

a The frequency range is 2 kHz to 3 kHz for 50 Hz systems and 2,4 kHz to 3 kHz for 60 Hz systems.

b The logarithm of the level decreases linearly with the logarithm of the frequency in the range 3 kHz to 9 kHz.

表2中给出了在40次谐波(最高)至9 kHz时高于40次谐波(不包括)的差分模式下电压畸变的兼容水平。

Table 2 – Compatibility levels for voltage distortion in differential mode.JPG


5、差分模式下的电压失真从9 kHz到150 kHz

5.1 9 kHz到30 kHz差分模式下的电压失真

限值:

Table 3 – Compatibility levels for voltage distortion in differential mode from 9 kHz to 30 kHz(a)

Frequency range(kHz) Compatibility levels(dB(µV))
9 to 30 1 29,5 to 1 22 b
3 to 9 1 ,4 to 0,65 b
  • a For EMC coordination in the setting of emission limits for unsymmetrical voltage distortion, see 4.1 2.1 .
  • b The level decreases linearly with the logarithm of the frequency in the range 9 kHz to 30 kHz.

5.2 30kHz到150 kHz差分模式下的电压失真

限值:

Table 4 – Compatibility levels for voltage distortion in differential mode from 30 kHz to 150 kHz a

Frequency range(kHz) Compatibility levels(dB(µV))
30 to 50 b 1 22 to 1 1 9 c
50 b to 1 50 1 1 3 to 89 c
  • a For EMC coordination in the setting of emission limits for unsymmetrical voltage distortion, see 4.1 2.1 .
  • b At the transition frequency, the lower level applies
  • c The level decreases linearly with the logarithm of the frequency in the ranges 30 kHz to 50 kHz and 50 kHz to 1 50 kHz.


4、电压暂降和短时中断


5、电压不平衡
6、瞬态过电压
7、短时电源频率变化
8、直流分量
9、电网信号

测试项目-电压波动和闪烁

谐波

本部分中, 谐波的兼容水平主要针对稳态和准稳态谐波, 并给出 其长期影响和短期影响的参考值。 长期影响主要指谐波在电缆、变压器、电动机、电容等设备上引起的热效应, 这主要由 持续时间10 min及以上的谐波水平引起。 短期影响, 主要指持续时间 3 s 及以 下的谐波水平对某些敏感设备的骚扰影响, 暂态不包括在内。

限值:

  • 对于长期影响, 对应的总谐波畸变的兼容水平为THD=8%
  • 对于短期影响, 单次电压谐波分量的兼容水平由 表 1 中的限值乘以系数 k , 此时, 对应的总谐波畸变的兼容水平为 THD =11%

测试项目- 间谐波

间谐波

测试项目- 电压暂降和短时中断

电压暂降和短时中断

测试项目- 电压不平衡

电压不平衡

测试项目- 瞬态过电压

瞬态过电压

测试项目- 短时电源频率变化

短时电源频率变化

测试项目- 直流分量

直流分量

测试项目- '电网信号

电网信号

对应国标

GB/T 18039.3-2017(IEC 61000-2-2:2002)

电磁兼容 环境 公用低压供电系统低频传导骚扰及信号传输的兼容水平

国家标准《电磁兼容 环境 公用低压供电系统低频传导骚扰及信号传输的兼容水平》由TC246(全国电磁兼容标准化技术委员会)归口上报,TC246SC2(全国电磁兼容标准化技术委员会低频现象分会)执行,主管部门为国家标准化管理委员会。

主要起草单位 中国电力科学研究院 、工业和信息化部电子第五研究所 。

主要起草人 刘兴发 、万保权 、邬雄 、尹婷 、张建功 、路遥 、朱文立 、张业茂 、谢辉春 、李妮 。

本标准等同采用IEC国际标准:IEC 61000-2-2:2002。